CO2 controller
ESTSP programmable CO2 detector with 0-10V or 4-20mA output
overview
- A new, low-cost, low-maintenance carbon dioxide detection or with powerful functions
- Perfect CO2 transmitter/controller
- CO2 measurement range: 0 to 2,000ppm (standard); 0 to 5,000ppm (optional)
- LED visual and audible alarms
- NDIR infrared CO2 sensor with patented ABC self-calibration
- One or two 0~10VDC /4~20mA linear outputs for CO2 or CO2 /Temp.
- PID control output selectable for CO2 measurement
- LED light selectable between 3-color mode and working mode
- Optional OLED screen displays measurements
- One relay output optional for a ventilator or a CO2 generator
- Buzzer alarm provided for the models with relay
- CE approval
A programmable CO2 detector and controller that is ideal for HVAC applications in schools, offices and other indoor workplaces.
The ESTSP measures CO2 and temperature with a relay control output or linear 0-10V/4..20mA to control ventilation units and variable speed drives.
The ESTSP is very easy to use and maintain. The ESTSP has an ABC style self-calibration with the ability to zero, or reset itself, for optimal accuracy. Therefore, the ESTSP can run for many years without extensive support or re-calibration. Alternatively, the team at Edaphic Scientific can re-calibrate the ESTSP for you, if required.
The Tongdy ES-TSP model is similar to the SenseAir tSense model and performs many of the same functions. The ES-TSP is a lower cost version of the tSense model and is ideal for many indoor air applications.
specifications
feature | specification |
---|---|
Carbon Dioxide Sensor | |
Sensing Element | NDIR |
Measurement Range | 0 to 2,000 ppm (standard) | 0 to 5,000 ppm (optional) |
Measurement Accuracy | ±60 ppm |
Response Time | <2 minutes for 90% step change typical |
Signal Update | Every 2 seconds |
Calibration | ABC Logic Self Calibration Algorithm |
General Specifications | |
Power Supply | 24 VAC/VDC |
Power Consumption | 3.5 W max. ; 2.0 W avg. |
Analog Outpus | One 0~10V DC /4~20mA for CO2 measurement | Two 0~10V DC /4~20 20mA for CO2/Temperature measurements PID control output is select able |
Relay Output | One passive relay output (max.5A) |
RS-485 Modbus Interface | Modbus protocol or BACnet protocol protocol, 4800/ 9600 (default )/19200/38400bps 38400bps; 15KV antistatic protection, independent base address. |
LED Screen Displays | Display CO2 or CO2/temp. or CO2/Temp./ RH measurements |
Operating Environment | 0~50℃; 0~95% non condensing |
Storage Environment | -10 ~60℃, 0~80%RH |
Weight and Dimensions | 190g | 117 mm (H) ×95mm ( ×36 mm(D) |
Installation | wall mounting |
Housing Material and IP Class | PC/ABS fireproof plastic material, protection class: IP30 |
Standard | CE approval |